• Certification parameters: 0.25-5 (80) A, Class B, 230 VAC 50 Hz, -25 °C to +55 °C, 4 quadrants in 2 tariffs.
• Class B (EN-50470 standard) – Active energy Class 2 (IEC 62053-23 standard) – Reactive energy
• Direct connection (up to 80 A)
• LCD display and 3 button keys (to display Energy, V, I, PF, F, P, Q and parameter configuration)
• LCD display with 8 digits. • Self powered (by the same input voltage)
• 2 DIN modules (36 mm) • 2 tariffs controlled by a 230 VAC digital input
• 2 MID certified standard S0 low voltage pulse outputs